Toll Free: (800) 836-0754
 
Phone: (585) 798-4300

Industrial Heaters & Heating > Constant Watt Electric Heat Trace

FE General Purpose Constant-Wattage Heating Cable
Product Highlights

  • Temperatures up to 400oF (204oC)
  • Power remains constant regardless of temperature
  • Can be cut-to-length at job site
  • Ideal for a wide range of general purpose applications
    • Mid-range process temperature control for food and chemical processing
    • Water lines
    • Fire protection systems
    • Fuel oil
    • Condensate return
    • Hot water lines
    • Lines periodically purged with 250 psig steam

Specifications

  • Maximum exposure temperature is 400oF (204oC)
  • Moisture, chemical, flame, and radiation resistant
  • 12AWG bus wires
  • Dimensions 0.2" x 0.3" (5 x 8mm)
  • 40 lb. (18kg) per 500-foot (152m) spool

    TEFLON® is a registered Trademark of DuPont used under license.

Approvals

  • Ordinary Locations
  • Hazardous Location (T3 rated):
    • Class I Division 2 Groups B, C, D
    • Class II Division 2 Groups F, G
    • Class III Division 2
  • Ordinary locations (120 and 240VAC only)  





KE Harsh Environment Constant-Wattage Heating Cable
Product Highlights

  • Temperatures up to 500oF (260oC)
  • Power remains constant regardless of temperature
  • Can be cut-to-length at job site
  • Ideal for a wide range of general purpose applications in corrosive environments:
    • Freeze protection
    • Viscosity control
    • High temperature process control
    • Asphalt plants
    • Oil refineries
    • Mines
    • Chemical and petrochemical processing areas
    • Other explosive and corrosive atmospheres
    • Severe arctic cold

Specifications

  • Maximum exposure temperature is 500oF (260oC)
  • Moisture, chemical, flame, and radiation resistant
  • 12AWG bus wires
  • Dimensions 0.2" x 0.3" (5 x 8mm)
  • 41 lb. (19kg) per 500-foot (152m) spool

    TEFLON® is a registered Trademark of DuPont used under license.

Approvals

  • Ordinary Locations
  • Hazardous Location (T3 rated):
    • Class I Division 2 Groups B, C, D
    • Class II Division 2 Groups F, G
    • Class III Division 2

Approval valid only when used with appropriate heating cable and installation accessories, and installed in accordance with all applicable instructions, codes, and regulations.



Constant Watt Electric Heat Trace





























Constant-Wattage Heating Cable

 


Contact Us - Site Map - Privacy Policy - Home
WebEssentials Website Design & Hosting